Related manuals

...

1 downloads 9266 Views 233KB Size

®

COBALT COBALT Plus COBALT Pro DIGITAL DUAL TECHNOLOGY MOTION DETECTOR cobalt_en 07/15

The COBALT / COBALT Plus / COBALT Pro detector allows detection of motion in the protected area. This manual applies to the detector with electronics version Q (or newer).

1. Features            

Passive infrared (PIR) sensor and microwave sensor. Dual [COBALT, COBALT Plus] or quad [COBALT Pro] element pyrosensor. Adjustable detection sensitivity of microwave sensor. Selectable detection sensitivity of passive infrared sensor. Digital motion detection algorithm. Digital temperature compensation. Selectable operation modes: basic or counting. Microwave based anti-mask feature [COBALT Plus / COBALT Pro]. Built-in EOL resistors (Double EOL). Bi-color LED to indicate motion detection / alarm status. Supply voltage control. Tamper protection against cover removal.

2. Description Operation modes Basic – the detector indicates an alarm if both sensors detect motion within a time period shorter than 10 seconds. Counting – the detector indicates an alarm if:  both sensors detect motion within a time period shorter than 10 seconds,  within 30 minutes' period, the microwave sensor detects motion 16 times, but PIR sensor does not detect any motion.

Anti-mask feature Detection by the microwave sensor of an object moving at a distance of 10-20 centimeters from the detector is interpreted as an attempt to mask the detector and results in activation of anti-masking relay for two seconds. Objects permeable to microwaves, but isolating the infrared radiation are not detected by the anti-mask feature.

Supply voltage control In the event of the voltage drop below 9 V (± 5%) for more than 2 seconds, the detector will signal a trouble. The trouble is indicated by the activation of alarm relay and the steady red light of LED indicator. The trouble signaling will continue as long as the trouble persists.

2

COBALT • COBALT Plus • COBALT Pro

SATEL

3. Electronics board terminals: WRN - anti-masking output (NC relay) [only COBALT Plus and COBALT Pro]. TMP - tamper output (NC). COM - common ground. 12V - power input. NC - alarm output (NC relay). configuration pins for detector outputs: the built-in resistors are to be used – place the jumpers as shown in Fig. 2 (connect the outputs as shown in Fig. 10), the built-in resistors are not to be used – place the jumpers as shown in Fig. 3 (connect the outputs as shown in Fig. 9). microwave sensor. bi-color LED to indicate: – alarm – the LED lights red for 2 seconds, – motion detected by one of the sensors – the LED lights green for 2 seconds, – trouble – the LED lights red, – warm-up – the LED is blinking alternately red and green. PIR sensor. Do not touch the pyroelectric sensor, so as not to soil it. tamper switch. detector configuration pins: PIR SENS. - selecting the PIR sensor sensitivity – see: Fig. 4 (A – low sensitivity, B and C – medium sensitivity, D – high sensitivity). MODE - selecting the detector operation mode (jumper installed – basic mode; jumper removed – counting mode). LED - enable/disable the LED indicator (jumper installed – LED enabled; jumper removed – LED disabled). potentiometer for adjustment of the microwave sensor sensitivity. Please bear in mind that microwaves can penetrate e.g. glass, gypsum walls, non-metallic doors, etc. fixing screw hole.

SATEL

COBALT • COBALT Plus • COBALT Pro

3

4. Installation

1. 2. 3. 4. 5.

Remove the front cover (Fig. 5). Remove the electronics board. Make the openings for screws and cable in the enclosure base. Pass the cable through the prepared opening. Secure the enclosure base directly to the wall or to the bracket screwed down to the wall/ceiling (Fig. 6 and 7). 6. Fasten the electronics board. 7. Connect the wires to the corresponding terminals. 8. Using potentiometer and jumpers, set the detector working parameters.

4

COBALT • COBALT Plus • COBALT Pro

SATEL

9. Replace the cover.

5. Start-up and walk test Note: When testing the detector, the LED should be enabled. 1. Power-up the detector. The LED will begin alternately blinking red and green, which indicates the detector warm-up. 2. When the LED stops blinking, check that moving within the coverage area will activate the alarm relay and make the LED light up red. Fig. 8 shows the maximum coverage area (maximum sensitivity).

6. Specifications Supply voltage ................................................................................................... 12 V DC ±15% Standby current consumption ..........................................................................................14 mA Maximum current consumption ........................................................................................20 mA EOL resistors .............................................................................................................2 x 1.1 k Relay contacts rating (resistive load) .............................................................. 40 mA / 16 V DC Microwave frequency ..............................................................................................10.525 GHz Detectable speed ...................................................................................................... 0.3...3 m/s Alarm signaling period........................................................................................................... 2 s Warm-up period .................................................................................................................. 30 s Recommended installation height ..................................................................................... 2.4 m Security grade according to EN50131-2-4 ...............................................................................II Operating temperature range..................................................................................-30...+55 °C Maximum humidity ..........................................................................................................93±3% Dimensions ................................................................................................... 63 x 136 x 49 mm Weight COBALT................................................ 136 g COBALT PLUS ..................................... 144 g COBALT PRO ....................................... 145 g

The declaration of conformity may be consulted at www.satel.eu/ce

SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND tel. 58 320 94 00 www.satel.eu